mag-flux HTL DN80
PRODUCT DESCRIPTION
DN 80 Water Meter; Hydrant Tester; mag-flux HTL
Portable hydrant tester for measuring flow and pressure (battery-powered, includes data logger)
- Magnetic-inductive flow meter
- No moving parts
- Unrestricted flow (no additional pressure losses)
- Includes pressure sensor
- Includes data storage for 2,000,000 measurements
- Data transmission via Bluetooth™ (in conjunction with the ANDROID / iOS wasserkarte.info app)
- 5-inch LCD display, backlit, 240 x 128 pixels, permanent display
- System languages: German, English, French, Italian
- High stability
Technical Specifications
Nominal diameter: DN 80 / 3"
Connection: Storz B, swivel
Operating pressure: -1 ... 16 bar
Fluid temperature: 1 ... 40 °C
Flow rate: 0 ... 217 m³/h (3,600 l/min)
Protection class: IP54
Battery: 2 built-in NiMH batteries, 7.2 V each
Battery life: up to 24 hours
Charging time: approx. 4 hours
Measurement accuracy: Flow ±0.5% ±2.0 mm of the measured value, pressure ±0.5% of the full-scale value
Dimensions (without Storz coupling): 260 x 250 x 320 mm (L x W x H)
Weight: approx. 14.8 kg